Alarm ranking at runtime

  • Last UpdatedFeb 19, 2025
  • 1 minute read

The most important alarm has the lowest severity number, but other criteria are taken into account when ranking alarms by urgency at run time.

Alarm Mode

Enabled is more urgent than silenced.

Alarm Shelved

FALSE (not shelved) is more urgent than TRUE (shelved).

InAlarm

TRUE (InAlarm) is more urgent than FALSE (normal).

Acked

FALSE (unacked) is more urgent than TRUE (acked).

Severity Level

1 is most urgent; 5 is least urgent. Severity 5 alarms only appear if the severity 4 priority range is set less than 999. The default upper is 999 for severity 4 alarms.