Alarm ranking at runtime
- Last UpdatedFeb 19, 2025
- 1 minute read
The most important alarm has the lowest severity number, but other criteria are taken into account when ranking alarms by urgency at run time.
|
Alarm Mode |
Enabled is more urgent than silenced. |
|
Alarm Shelved |
FALSE (not shelved) is more urgent than TRUE (shelved). |
|
InAlarm |
TRUE (InAlarm) is more urgent than FALSE (normal). |
|
Acked |
FALSE (unacked) is more urgent than TRUE (acked). |
|
Severity Level |
1 is most urgent; 5 is least urgent. Severity 5 alarms only appear if the severity 4 priority range is set less than 999. The default upper is 999 for severity 4 alarms. |