Enable alarm shelving
- Last UpdatedJan 16, 2025
- 1 minute read
Alarm shelving is configured from the Galaxy Configuration menu, and is enabled on the Area object.
To enable alarm shelving
-
Enable at least one security role to configure alarm shelving. Associate the relevant user with that role, if not already associated, before proceeding to step 2.
-
Select the Galaxy menu item, then select Configure.
-
Select Galaxy, then select Alarms. The Alarms page appears.

-
Select the severity level in the Shelve column. By default, severity levels 3 (medium) and 4 (low) are enabled.
-
In the IDE, open the relevant Area object editor. Select the Shelve Alarms checkbox to enable shelving for that area. Shelving is enabled by default.