Set alarms on the attributes page

  • Last UpdatedJan 16, 2025
  • 1 minute read

You set alarms for all Application Server objects in the Attributes page in the Object Editor.

To specify alarms for an object’s attributes

  1. On the Attributes page of the Object Editor, select an attribute from the Attributes List.

    Limit alarm configuration

  2. Select the alarm features you want to configure for the attribute. For Boolean data types, you can select:

    • I/O Alarm

    • State alarm

    • Bad value alarm

    For Integer, Float and Double data types, you can select:

    • Limit alarms

    • ROC alarms

    • Deviation alarms

    • Bad value alarms

    Note: Depending on the object type, some of these alarm types may not be available.

  3. For each alarm feature that you activate, enter the settings for each alarm.

    1. Assign values to the alarm limits based on the type of alarm.

    2. Assign an alarm priority (1-999) for each limit you set.

    3. Accept the default alarm message or include another message for each alarm limit.

    4. Assign values to the remaining attributes based on the type of alarm you selected. For more information about other alarm attributes, see Types of alarms.

  4. To configure event logging for an object, select the Log change feature and select the checkbox Log system events in addition to user events.

  5. Save your object changes and close the Object Editor.