Set alarms on the attributes page
- Last UpdatedJan 16, 2025
- 1 minute read
You set alarms for all Application Server objects in the Attributes page in the Object Editor.
To specify alarms for an object’s attributes
-
On the Attributes page of the Object Editor, select an attribute from the Attributes List.

-
Select the alarm features you want to configure for the attribute. For Boolean data types, you can select:
-
I/O Alarm
-
State alarm
-
Bad value alarm
For Integer, Float and Double data types, you can select:
-
Limit alarms
-
ROC alarms
-
Deviation alarms
-
Bad value alarms
Note: Depending on the object type, some of these alarm types may not be available.
-
-
For each alarm feature that you activate, enter the settings for each alarm.
-
Assign values to the alarm limits based on the type of alarm.
-
Assign an alarm priority (1-999) for each limit you set.
-
Accept the default alarm message or include another message for each alarm limit.
-
Assign values to the remaining attributes based on the type of alarm you selected. For more information about other alarm attributes, see Types of alarms.
-
-
To configure event logging for an object, select the Log change feature and select the checkbox Log system events in addition to user events.
-
Save your object changes and close the Object Editor.