Point a redundant interface to a secondary collective member
- Last UpdatedJan 13, 2023
- 2 minute read
If you just upgraded from a single Data Archive server to a collective, restart PI ICU.
If you use PI Buffer Subsystem 4.3 or later, follow steps 1 through 4 below. If you use PI Buffer Subsystem versions 3.4.380 and earlier, follow all steps below.
-
In the PI ICU page tree, select General.
-
Under PI Host Information, set SDK Member to a secondary collective member.
This property sets which Data Archive server in the collective sends the interface configuration information and output points. If you set each interface to a different collective member, you enable failover when the Data Archive server that sends output points becomes unavailable.
-
Set API Hostname to match.
The interface uses this information to connect to the Data Archive server that provides configuration data.
The drop-down list shows the host specified in various formats. You can specify the host as an IP address, a path, or a host name. However, when you configure the buffered server list, you must specify the buffered server names in the same format, otherwise buffering will not work.
-
Click Apply.
Note: Follow the remaining steps only if you are using PI Buffer Subsystem 3.4.380 or earlier.
-
Select Tools > Buffering.
-
In the Buffering dialog box task list, select Buffered Servers.
-
Verify that the Replicate data to all collective member nodes check box is selected and that the server list contains the server and format specified in API Hostname.
-
If necessary, click the appropriate entry under Buffered Server Names to change the format.
-
Click Yes at the prompt to restart PI Buffer Subsystem and dependent interfaces.