Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Instrumentation

Auto-Cable Drum

  • Last UpdatedNov 03, 2025
  • 2 minute read

Wiring Manager supports auto-cable drumming: the assignment of cables to cable drums using an algorithm to minimize any unused cable based on each cable's length and the catalog drum length.

Note: Cables can also be added to drums when cables drums are being created or edited (see Create Cable Drums Manually), or manually from the Cable Schedule (see Assign Cables to Drums from the Cable Schedule).

  1. From the Cable Schedule grid, select the cables to be drummed.

  2. Click Auto-Cable Drum selected Cables in the Actions section of the List Tools - Cable Schedule tab.

    Only cables with a status of New or Replace will be auto-drummed. Also, cables marked as Vendor Supplied, or with a length of 0 will not be auto-drummed. A message is displayed to remind users of this:

  3. Click OK.

    The Auto-Cable Drumming Options window is then displayed:

    The available options are:

    • Allow cables already Drummed to be Reassigned: if this option is selected, Wiring Manager may 'move' cables between drums to help minimize cable wastage.

    • Allow Wiring Manager to create new Cable Drums (if needed): if this option is selected, Wiring Manager may create enough new drums to assign all cables. If no drums have been created then this option must be selected.

  4. Select the required options and click Auto Drum.

    Wiring Manager then analyzes the selected cables and any existing drum assignments, creates the minimum number of drums and then assigns each selected cable to a drum in such a way as to minimize any unused cabling on each drum. New drums are added to the Cable Drum Schedule.