Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Simulation for Foxboro Control

Generating the SCP Scenario File

  • Last UpdatedMar 10, 2020
  • 1 minute read

A SCP scenario file is required to capture actions from the workstation (WSTA). For convenience, a sample file based on the DEMO controls set has been included with the installation and resides in the default directory:

C:\SIMSCI\DSS6x\Simulations\<your simulation>\scpeng.sce

A sample configuration of the "scpeng" scenario file is shown below:

DEMO:MOTOR_CTRL.BI01,0.5,,

DEMO:MOTOR_CTRL.BI02,0.5,,

DEMO:LVL_CTRL.MA,0.5,,

DEMO:LVL_CTRL.SPT,0.01,,

DEMO:LVL_CTRL.OUT,0.01,M,

DEMO:DISCH_DMD.MA,0.5,,

DEMO:DISCH_DMD.MEAS,0.5,

DEMO:DISCH_DMD.OUT,0.5,M ,

This file is made up of rows, separated by commas that include:

  • Controls specific <compound>:<block>.<parameter>

  • Tolerance

  • Auto/Manual (optional)

  • Remote/Local (optional)

The scenario records an action of the variable if the absolute value of the change is greater than that of the tolerance.

The scenario file name and location can be modified in the Engine Configuration window.