Configuring Physical I/A Series MESH Connection to SCP VMs
- Last UpdatedMay 13, 2020
- 1 minute read
You may connect physical I/A Series systems to the Hyper V Server containing the SCP virtual machine.
Follow these "quick reference" steps.
I/A Series systems require two physical connections to the MESH network. Since SCP can only make one connection to the MESH network, a switch is required to interface the I/A Server with the SCP VM.
See the diagram below for an illustrated view:

Figure A - 1
The physical I/A Series suite requires two network connections (cables) to the switch. The Hyper-V (SCP) should include one connection. Both systems can also include one connection from the ACN network that might go to a company LAN or another network.
IMPORTANT: DO NOT PLUG THE ACN NETWORK INTO THE MESH SWITCH.