Individually download each CP to the SCP station(s). If validation errors occur, such as a requirement to compile PLBs, or assign the correct WSTA host, the IACC application provides feedback.

  1. Verify the process model is up and frozen with an SCP engine.

  2. Within the IACC, click the Network pane, expand the tree, and navigate to a CP.

  3. Right-click the CP. From the context menu, select Validate/Download, and then click Download.

    Embedded Image (65% Scaling) (LIVE)

  4. In the Hierarchy Validation window, click Next.

    Embedded Image (65% Scaling) (LIVE)

  5. In the Validating window, click Next.

    Embedded Image (65% Scaling) (LIVE)

  6. In the Control Station Download window, click the Select All button, and then click Next.

    Embedded Image (65% Scaling) (LIVE)

  7. Review the feedback in the IACC Download Summary pane.

  8. Repeat this for each CP.

  9. Run the process model for several seconds to allow each block to process, and then freeze.

  10. Refresh FoxSelect / BlockSelect and verify all compounds are turned on. If not, turn them on, and then run/freeze.

  11. Within FoxSelect / BlockSelect, sort on Block Status to verify that the blocks are good.