Synchronizing Unit Equipment Deployment State
- Last UpdatedApr 20, 2020
- 1 minute read
If the restored Galaxy Database was in the "deployed" state, you need to change the state to "undeployed" using the Deploy Utility’s "Synchronize Deploy Status" option. Note that this process can be quite time consuming. We recommend that you perform this step individually on each piece of equipment first, then select the main Equipment Unit, deselect all equipment that was previously synchronized, and synchronize the Equipment Unit as described below.
-
Start the ArchestrA IDE via Start > Programs > Wonderware > ArchestrA IDE.
-
In the ArchestrA IDE, view the Network pane.
-
Verify that all equipment is checked in (look for red checkmarks). If the object was checked out in a different session, right-click it and then click Check In.
-
In the Network Pane, locate any equipment that is marked as deployed or partially deployed. Right-click on the equipment, select Deploy Utilities, and then click Synchronize Deploy Status.
-
Click Undeploy and then synchronize the status.