AlarmFirstCatRec

  • Last UpdatedJul 18, 2023
  • 2 minute read

Searches for the first occurrence of an alarm category and type. You can search all areas, the current area only, or specify an area to limit the search.

This function returns an alarm record identifier that you can use in other alarm functions, for example, to acknowledge, disable, or enable the alarm, or to get field data on that alarm.

Note: Record numbers obtained from AlarmGetDsp are not valid for this function.

This is a blocking function. If the function is called from a foreground task that is unable to block, the return value will be -1 and a hardware alarm set. Use IsError() to retrieve the error code.

Syntax

LONG AlarmFirstCatRec(INT Category, INT Type [, INT Area] [, STRING ClusterName] )

Category:

The alarm category or group number to match. Set Category to 0 (zero) to match all alarm categories.

nType:

The type of alarms to display:

Non-hardware alarms

0 - All active alarms, that is Types 1 and 2

1 - All unacknowledged alarms, ON and OFF

2 - All acknowledged ON alarms

3 - All disabled alarms

4 - All configured (non-hardware) alarms, that is Types 0 to 3, plus acknowledged OFF alarms.

Alarm General

11 - All ON alarms

12 - All OFF alarms

17 - All unacknowledged ON alarms

18 - All unacknowledged OFF alarms

If you omit the Type, the default is 1.

Note: If you call this function with the Type argument set to an unsupported value, it may return unexpected results.

Area:

The area in which to search for alarms. If you do not specify an area, or if you set Area to -1, only the current area will be searched.

ClusterName:

Specifies the name of the cluster in which the Alarm Server resides. This is optional if you have one cluster or are resolving the alarm server via the current cluster context. The argument is enclosed in quotation marks "".

Return Value

The alarm record identifier or -1 if no match is found.

GrpOpen, AlarmNextCatRec, AlarmFirstPriRec, AlarmNextPriRec, AlarmGetFieldRec, AlarmAckRec, AlarmDisableRec, AlarmEnableRec, AlarmGetThresholdRec, AlarmSetThresholdRec

Example

See AlarmAckRec