[IOServer]AlwaysCallStopChannel

  • Last UpdatedJul 19, 2023
  • 1 minute read

Determines whether Plant SCADA attempts to call the StopChannel() function for a driver.

The StopChannel call releases resources allocated for a PLC connection. Under normal circumstances, this occurs when the PLC is online at shutdown, or disabled. Since the PLC may not get a StopChannel when it is offline at shutdown, its resources may not have been released and Plant SCADA crashes can occur.

By default this parameter is set to 1which means that a StopChannel is called, and may prevent crashes at shutdown. Usually if setting AlwaysCallStopUnit, you would set AlwaysCallStopChannel.

Allowable Values:

  • 0 - StopChannel is not called.

  • 1 - StopChannel is called.

Default Value:

1