AVEVA™ Plant SCADA

Alarm Light

  • Last UpdatedJul 18, 2023
  • 2 minute read

The alarm light object is a text object used to draw the operator’s attention to an alarm that may not have a numerical equivalent (for example, LOW FIRE CHECK).

When the alarm is inactive, the text is barely visible so as to not draw the operator’s attention to the text, but still makes the operator aware that there is an alarm associated with a piece of equipment. If the alarm is triggered, the visibility will be forced to "on".

Property

Description

Name

Alarm Light

Graphical Representation

Associated Composite Genie

AlarmLight.xml

Configuration Tasks

  • Add Equipment Using Equipment Editor: Create equipment instances for the required objects, and organize the equipment in a hierarchy. Objects can be referred to by their name when you add Composite Genies to a graphics page. You can add one or more instances of an equipment to a page.

  • Configure PLC Limits with Equipment: This is an optional task that is required if you want to use PLC alarm limits instead of the standard analog alarm limits.

  • Insert a Composite Genie: Create graphics pages with instances of Composite Genies that are associated with the equipment you have defined in your project.

  • Create a New Faceplate: Add a Faceplates for the equipment to allow operators to engage with the equipment at runtime.

  • Write Cicode functions to initialize PR and OR values. Refer to the Cicode Reference documentation for more information.

Presentation Options

The following presentation options are available for this object.

Option

Description

Equipment Name

Enter the name of the equipment associated with the object. You can enter a maximum of 160 characters for this option.

Item Name

Item Name of the alarm for which to display the status. You can enter a maximum of 63 characters for this option.

Size

Size of the alarm light object image - small or large

Label

Text that describes the alarm condition. You can enter a maximum of 30 characters for this option.

Display Alarm Indicator

Select this option to display an alarm indicator that indicates the highest priority alarm and its state for this Alarm Light equipment object.

Display Alarm Flag

Select this option to display an alarm flag. This option is available for selection only if the Display Alarm Border option is selected.

Display Status Indicator

Select the location to display a status indicator. Select None if you do not wish to see the status indicator. For more information, see Status Indicators.