[Alarm]TransferInterval

  • Last UpdatedJul 19, 2023
  • 1 minute read

Defines the number of seconds between each attempt to update the data on the Standby server. For many systems, you will not need to change the default setting of 5 seconds.

If you have a large system, the Primary server may be affected by a high load due to a high number of updates placing a large demand on the server’s resources. If your system is experiencing slow performance, you may need to increase the TransferInterval so that the Primary server updates the Standby server less frequently. If the data on the Standby server is being updated too slowly, you may need to decrease the TransferInterval so that updates occur more frequently. Be aware that this may affect the load on the Primary server and so could lead to slow performance.

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

0 to 4294967295

Default Value:

5