[Alarm]SummaryTimeout

  • Last UpdatedJul 19, 2023
  • 1 minute read

The length of time after which an alarm summary entry is considered timeout.

The alarm system searches for timeout entries in the order of On time from oldest to newest. The search may stop or skip entries depending on the value of parameter [Alarm]SummaryMode.

The found timeout entries are then committed to the Summary Devices specified in the alarm categories of the entries.

Refer to the Cicode function AlarmSumCommit for committing process.

You can disable this parameter by setting it to -1.

This parameter is modified by the Computer Setup Wizard as well as the Computer Setup Editor.

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

0 to 20000 (minutes)

Default Value:

60

See Also

Alarm Parameters