[Alarm]IsolationDetectInterval

  • Last UpdatedJul 19, 2023
  • 1 minute read

This parameter sets the interval between Internet Control Message Protocol (ICMP) packets to detect network isolation on alarm servers. If the ICMP check fails to get a response in a row as configured on [Alarm]IsolationDetectRetryCount parameter, the server will regard itself as isolated and switch itself to an isolated main state.

This parameter is only valid if [Alarm]IsolationDetectIP1 and/or [Alarm]IsolationDetectIP2 parameters have been configured.

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

Length of time in milliseconds (500 - 120000)

Default Value:

5000 (5 seconds)