The values provided in this section are recommended default values for SCADA usage. They can be adapted depending on project needs.

OFS version

Use the latest version of OFS that is available. This information targets OFS V3.35, or greater.

Processor affinity

In multi-processor machines, set the processor affinity of the OFS server so that it does not run on the same processor as the Plant SCADA I/O Server.

Device Settings

These settings can be adjusted on a device-by-device basis (see Device Settings).

Communications settings

  • Sampling rate on reception

  • Minimum group update rate

  • QuickSetActive

  • Communication Overrun behavior

See Communications Settings.

In summary, the recommended OFS parameter settings for optimal performance are as follows:

Parameter

Recommended Setting

Communication Overrun behavior

Rate adapt

MaxChannels

Equipment dependent, set to the same as the MaxPending value calculated by OFS.

MaxPending

0 (Equipment dependent. OFS to calculate a value).

Minimum group update rate

Rate <= Fastest Group rate / 2, and

Rate is the greatest common divisor of the group rates (provided this doesn’t violate the previous rule).

OFS version

3.35 or later

Processor affinity

Different to Plant SCADA I/O server

QuickSetActive

True

Sampling rate on reception

20ms