M340, TSX Quantum and Premium PLCs - Data Types

  • Last UpdatedJul 08, 2025
  • 2 minute read

Data Types

Valid Address Range

Address Format

Plant SCADA Data Type

Output Coils

000001 - 065536

<valid address>
(e.g. 01000)

DIGITAL

Output Coils (Memory)

000001 – 065536

%M<valid address>
(e.g. %M7)

DIGITAL

Input Status

100001 - 165536

<valid address>
(e.g. 11001)

DIGITAL

Input Registers

300001 - 365536

<valid address>
(e.g. 31350)

INT/ REAL/ LONG/ BCD/ LONGBCD

Input Registers (DIGITAL)

300001 - 365536

<valid address>.b
where b is the bit number between 1 and 16 inclusive
(e.g. 32300.2)

DIGITAL

Output Holding Registers (ANALOG)

400001 - 465536

<valid address>
(e.g. 41190)

INT/ REAL/ LONG/ BCD/ LONGBCD

Output Registers (Memory)

000001 – 065536

%MW<valid address>
(e.g. %MW3)

INT/ REAL/ LONG/ BCD/ LONGBCD

Output Holding Registers (DIGITAL)

400001 - 465536

<valid address>.b
where b is the bit number between 1 and 16 inclusive
(e.g. 40001.4)

DIGITAL

Output Registers (DIGITAL) (Memory)

000001 – 065536

%MW<valid address>.b
where b is the bit number between 1 and 16 inclusive
(e.g. %MW4.6)

DIGITAL

Extended registers

EF:R
where:

E denotes the extended register.

F is the file number between 1 and 16 inclusive.

R is the register between 0 and 9999 inclusive.

INT/ REAL/ LONG/ BCD/ LONGBCD/ STRING

Individual Output Coil Register

000001 – 065536

G<valid address>
(e.g. G001000)

DIGITAL

Individual Input Coil Status

100001 – 165536

G<valid address>
(e.g. G103000)

DIGITAL

Individual Input Register

300001 – 365536

G<valid address>
(e.g. G301350)

INT / REAL / LONG / BCD / LONGBCD / STRING

Individual Output Register

400001 – 465536

G<valid address>
(e.g. G401190)

INT / REAL / LONG / BCD / LONGBCD / STRING

Individual Extended Register

G<EF:R>

where:

E denotes the extended register.

F is the file number between 1 and 16 inclusive

R is the register between 0 and 9999 inclusive

INT/ REAL / LONG / BCD / LONGBCD / STRING

Note: When writing DIGITAL variables to output registers, the individual bits in a register (1..16) can be written to with the format n.BitPosition (e.g. 40001.1). Writing to sequential bits requires individual write commands. The user can specify the bit order direction in the INI parameter [MODNET]RegisterBitReverse.

EXAMPLES

Data Type

DIGITAL

Address

00036

Comment

Output Coil

Data Type

LONGBCD

Address

30019

Comment

Input Register