Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

OMFINS Parameters

  • Last UpdatedJan 13, 2022
  • 2 minute read

warning2

UNINTENDED EQUIPMENT OPERATION

Do not change these protocol parameters, except on the advice of Technical Support for this product.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Note: Always seek the advice of Technical Support personnel for this product regarding undocumented features.

[OMFINS]Block

A value (bytes) used by the I/O Server to determine if two or more packets can be blocked into one data request before being sent to the I/O Device. For example, if you set the value to 10, and the I/O Server receives two simultaneous data requests - one for byte 3, and another for byte 8 - the two requests will be blocked into a single physical data request packet. This single request packet is then sent to the I/O Device, saving on bandwidth and processing.

Allowable Values 5 to 256

Default Value 64

[OMFINS]Delay

The period (in milliseconds) to wait between receiving a response and sending the next command.

Allowable Values 0 to 300 (milliseconds)

Default Value 0

[OMFINS]IgnoreNonFatalError

Determines whether Plant SCADA will stay online if the remote rack is powered off.

Allowable Values 0 (recoverable errors not ignored) or 1 (recoverable errors ignored)

Default Value 0

[OMFINS]MaxPending

The maximum number of pending commands that the driver holds ready for immediate execution.

Allowable Values 1 to 32

Default Value 2

[OMFINS]PollTime

The interrupt or polling service time (in milliseconds). Setting the polling time to 0 puts the driver in interrupt mode.

Allowable Values 0 to 300 (milliseconds)

Default Value 0

[OMFINS]Retry

The number of times to retry a command after a timeout.

Allowable Values 0 to 8

Default Value 1

[OMFINS]Source

Specify the FINS network address, node number and unit number for the Plant SCADA I/O server. This will be the source address of messages from Plant SCADA, and the destination address of responses from the PCs.

Format w/n/u where:

w is s the FINS network address (1-127)

n is the FINS node number (1-126)

u is the FINS unit number (0-15)

Default Value 1/1/0

[OMFINS]Timeout

Specifies how many milliseconds to wait for a response before displaying an error message.

Allowable Values 0 to 32000 (milliseconds)

Default Value 1000

[OMFINS]WatchTime

The frequency (in seconds) that the driver uses to check the communications link to the I/O Device.

Allowable Values 0 to 128 (seconds)

Default Value 30