Control Data Types - Binary Outputs

  • Last UpdatedAug 04, 2025
  • 2 minute read

This table defines the Plant SCADA variable address required for the specified DNP3 data types.

Address

Plant SCADA Type

DNP3 Type

Description

BO<n>.Select.Latch

DIGITAL

Binary Output Control

Select (Latch Mode)

Object 12 Variation 1

W/O.

Selects point and mode of operation (the driver will automatically send out the corresponding operate command).

Maintains output in specified state.

BO<n>.Select.Pulse

DIGITAL

Binary Output Control

Select (Pulse Mode)

Object 12 Variation 1

W/O.

Selects point and mode of operation (the driver will automatically send out the corresponding operate command).

Only Pulse ON supported.

BO<n>.Select.TC

DIGITAL

Binary Output Control

Select (TC Mode)

Object 12 Variation 1

W/O.

Selects point and mode of operation (the driver will automatically send out the corresponding operate command).

Trip and Close both use the ONTIME parameter.

0=Trip breaker,
1=Close breaker.

BO<n>.Operate.Latch

DIGITAL

Binary Output Control

Operate (Latch Mode)

Object 12 Variation 1

W/O.

Activates previously selected operation.Maintains output in specified state.

BO<n>.Operate.Pulse

DIGITAL

Binary Output Control

Operate (Pulse Mode)

Object 12 Variation 1

W/O.

Activates previously selected operation.

Only Pulse ON supported

BO<n>.Operate.TC

DIGITAL

Binary Output Control

Operate (TC Mode)

Object 12 Variation 1

W/O.

Activates previously selected operation.

Trip and Close both use the ONTIME parameter.

1=Close breaker,
0=Trip breaker.

BO<n>.SelectOnly.Latch

DIGITAL

Binary Output Control

Select (Latch Mode)

Object 12 Variation 1

W/O.

Selects point and mode of operation but does not operate.

Maintains output in specified state.

BO<n>.SelectOnly.Pulse

DIGITAL

Binary Output Control

Select (Pulse Mode)

Object 12 Variation 1

W/O.

Selects point and mode of operation but does not operate.

Only Pulse ON supported.Pulse OFF may be supported in future release.

BO<n>.SelectOnly.TC

DIGITAL

Binary Output Control

Select (TC Mode)

Object 12 Variation 1

W/O.

Selects point and mode of operation but does not operate.

Trip and Close both use the ONTIME parameter.

0=Trip breaker,
1=Close breaker.

BO<n>.DOperate.Latch

(See Note below)

DIGITAL

Binary Output Control

Direct Operate (Latch Mode)

Object 12 Variation 1

W/O.

Selects and activates point operation.Maintains output in specified state.

BO<n>.DOperate.Pulse

(See Note below)

DIGITAL

Binary Output Control

Direct Operate (Pulse Mode)

Object 12 Variation 1

W/O.

Selects and activates point operation.

Only Pulse ON supported.

BO<n>.DOperate.TC

(See Note below)

DIGITAL

Binary Output Control

Direct Operate (TC Mode)

Object 12 Variation 1

W/O.

Selects and activates point operation.

Trip and Close both use the ONTIME parameter.

1=Close breaker,
0=Trip breaker.

BO<n>.Configure.Ontime

LONG

Binary Output Control Configure Ontime

Object 12 Variation 1

W/O.

Time in milliseconds of momentary contact closure.

(Used in Pulse ON, Trip and Close modes).

BO<n>.CancelSel

DIGITAL

Binary Output Control Cancel Current SelectOnly

W/O.

Clear OPERATE status bits and cancel the SELECT operation to the RTU.

where:

  • n = Point index number (range from 0 to 2048)

  • R/O = read only

  • W/O = write only

  • R/W = read or write

Note: DNP (Subset level 1) supports a ‘Direct Operate without acknowledgment’, but as this does not verify the success of the command, only ‘Direct Operate’ is currently implemented.