GE Fanuc GE9030 via TCP/IP - Communication Settings

GE Fanuc GE9030 via TCP/IP - Communication Settings

  • Last UpdatedAug 04, 2025
  • 1 minute read

To establish communication with a device, the associated Board, Port and I/O Device need to be correctly configured in Plant SCADA Studio's Topology activity.

If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to manually configure them, use the settings outlined below.

Boards

Typically, you would use a normal Ethernet card for this communication. Complete the Board settings with the following specific information.

Field

Value

Board Name

Enter TCPIP.

Adress

Enter zero (0).

I/O Port

Leave this field blank.

Interrupt

Leave this field blank.

Special Options

Leave this field blank.

Ports

Field

Value

Port Name

Any unique number

Baud Rate

Leave this field blank.

Data Bits

Leave this field blank.

Stop Bits

Leave this field blank.

Parity

Leave this field blank.

Special Options

Enter the destination IP address of Ethernet module. Use the following format:

-Ia -Pn -T

where:

a = the destination IP address in standard Internet dot format. (For example 192.9.2.60)

n = the destination Port number. Often one physical port has several virtual ports, used for different purposes. Use this option only if you want to override the default of 18245.

-T = forces the driver to use TCP (the default), rather than UDP (-U).

I/O Devices

Field

Value

Address

Leave this field blank.

Protocol

Enter GETCP30.