Supported OPC DA Server Interfaces

  • Last UpdatedJul 13, 2023
  • 1 minute read

The following table indicates which OPC DA interfaces are supported by the Plant SCADA OPC DA Server. A highlighted field indicates that the particular OPC API is supported by the server.

OPC DA Server
required interfaces

Version 1.0

Version 2.0

Version 3.0

OPC Server

IUnknown

Required

Required

Required

IOPCServer

Required

Required

Required

IOPCCommon

N/A

Required

Required

IConnectionPointContainer

N/A

Required

Required

IOPCItemProperties

N/A

Required

N/A

IOPCBrowse

N/A

N/A

Required

IOPCServerPublicGroups

Optional

Optional

N/A

IOPCBrowseServerAddressSpace

Optional

Optional

N/A

IOPCItemIO

N/A

N/A

Required

OPC Group

IUnknown

Required

Required

Required

IOPCItemMgt

Required

Required

Required

IOPCGroupStateMgt

Required]

Required

Required

IOPCGroupStateMgt2

N/A

N/A

Required

IOPCPublicGroupStateMgt

Optional

Optional

N/A

IOPCSyncIO

Required

Required

Required

IOPCSyncIO2

N/A

N/A

Required

IOPCAsyncIO2

N/A

Required

Required

IOPCAsyncIO3

N/A

N/A

Required

IOPCItemDeadbandMgt

N/A

N/A

Required

IOPCItemSamplingMgt

N/A

N/A

Optional

IConnectionPointContainer

N/A

Required

Required

IOPCAsyncIO

Required

Optional

N/A

IDataObject

Required

Optional

N/A

See Also