Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

[Alarm]DBLogServerCore

  • Last UpdatedJul 19, 2023
  • 1 minute read

Use this parameter to enable logging for the analysis of redundancy and synchronization issues.

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

An integer representing one of the following logging masks, or the sum total of integers representing multiple logging masks:

Logging Mask

Description

Integer

DBERR

Server errors

1

DBSTD

Server state management

2

DBTRN

Server transaction

4

DBDRV

Server driver control

8

DBADV

Server advise links

16

DBSVR

Server and threads

256

DBSLT

Standby links

512

DBSCX

Links

1024

DBDA

OPC DA links

2048

DBHDA

OPC HDA links

4096

DBAE

OPC AE links

8192

DBMAN

Manager links

16384

DBDIA

Diagnostic links

32768

DBLRW

Link read-write

524288

SBXFR

Standby transfer

16777216

SBDAT

Standby transfer data

33554432

SBPOL

Standby polls

67108864

SBPEX

Standby poll details

134217728

DBSLR

Server link reference counting

536870912

Default Value:

0 (logging is not enabled)

Example

To enable logging of server errors (set using "1") and server transactions (set using "4"), you would add the integers for each and set the parameter to the following:

[Alarm]DBLogServerCore=5

See Also

[Alarm]DBLogDBServer

[Alarm]DBLogHistoric

Alarm Parameters