AVEVA™ Plant SCADA

[Alarm]DefSOEFmt

  • Last UpdatedJun 11, 2024
  • 1 minute read

Specifies an SOE display format to use if the display fields are not defined via the [Format]FormatName parameter and the SOE Format field for the Alarm Categories properties is blank.

If the alarm SOE formats are the same, set your alarm SOE format once using this parameter (instead of repeating the format many times in the Alarm Categories database). You would then save memory and increase the performance of your project.

Note: You can also change the font and format of the system events on the SOE page using the SOE Format field for alarm category 0 (zero).

Allowable Values:

Any combination of Alarm SOE Fields.

Default Value:

{DATE,16} {TIME,16} {TAG,10} {NAME,15} {MESSAGE,64} {STATE,16} {CLASSIFICATION,13} {USERNAME,16} {USERLOCATION,16}