XY Bar Graph

  • Last UpdatedFeb 02, 2024
  • 3 minute read

The XY Bar Graph object can be used to compare sets of related PV values from similar equipment.

Property

Description

Name

XY Bar Graph

Graphical Representation

Example Equipment Template

BarGraph

Associated Composite Genie

XY Bar Graph.XML

Equipment.Item Names Associated with the Genie

PRHigh, PRLow (see Meter Common Elements)

ORHigh, ORLow, ORDsp (see Meter Common Elements)

EqStatus (see Status Indicators)

Equipment Parameters the Equipment Items Expect

EqStatusFunc

Range

See Equipment Configuration Parameters

Configuration Tasks

  1. Add Equipment Using Equipment Editor: Create the equipment for the required objects. Organize the equipment in a hierarchy. Objects can be referred to by their name when you add Composite Genies to a graphics page. You can add one or more instances of an equipment to a page.

  2. Equipment References: Create the required relationships (equipment references) between a piece of equipment to items of another piece of equipment. This allows you to refer to equipment.items outside of the equipment hierarchy.

  3. Configure PLC Limits with Equipment: This is an optional task that is required if you want to use PLC alarm limits instead of the standard analog alarm limits.

  4. Insert a Composite Genie: Create graphics pages with instances of Composite Genies that are associated with the equipment you have defined in your project.

  5. Create a New Faceplate: Add a faceplate for the equipment to allow operators to engage with the equipment at runtime.

  6. Write Cicode functions to initialize PR and OR values. Refer to the Cicode Reference documentation for more information.

Presentation Options

The following presentation options are available for this object.

Option

Description

Main Equipment Name

Enter a name for the equipment associated with the XY Bar Graph. You can enter a maximum of 160 characters for this option.

Note: The XY Bar Graph equipment needs to be Define Equipment References each equipment to be monitored.

Main Equipment Item Prefix

Prefix applied to the main equipment item name. This allows for displaying multiple values for a single piece of equipment.

Number of Bars

Select the number of bars to be displayed in the graph. You can select a minimum of 1 and a maximum of 5 bars

Bar #n Equipment Name

Enter the name of each equipment to measure. The number of Bar #n Equipment Name options displayed depends on the Number of Bars selected for display. A maximum of 5 pieces of equipment can be selected for monitoring.

You can enter a maximum of 160 characters for this option.

Bar #n Equipment Item Prefix

Prefix applied to the equipment item name on each bar of the XY Bar Graph. This allows for displaying multiple values for a single piece of equipment.

Size

Size of the XY Bar Graph object image - small or large

Label

Enter the text that will display for the XY Bar Graph. You can enter a maximum of 30 characters for this option.

Display Alarm Indicator

Select this option to display an alarm indicator, which indicates the highest priority alarm and its state for this XY Bar Graph. The XY Bar Graph will also include alarms from each equipment included for comparison if you create an equipment reference between the XY bar Graph and each equipment specified for the bars.

Display Alarm Flag

Select this option to display an alarm flag. This option is available for selection only if the Display Alarm Border option is selected.

Display Status Indicator

Select the location to display a status indicator. Select None if you do not wish to see the status indicator. For more information, see Status Indicators.