[Alarm]DeltaTimeUpdate

  • Last UpdatedJul 19, 2023
  • 1 minute read

Determines whether the DeltaTime (duration) field is set on non-OFF alarms, by calculating volatile duration between current time and the time when the alarm was activated. Thus providing you with a snapshot of the duration of alarms. This parameter is for display clients and does not affect server side or the alarm database.

Note: The deltatime field set by this parameter is not refreshed until a new event on an alarm is made, such as a new alarm, state change on an existing alarm or page navigation. For the deltatime to refresh automatically, you will need to implement auto-page refresh using Cicode functions.

Allowable Values

  • 0 - (Disable)

  • 1 - (Enable)

Default Value:

0