Allen-Bradley PLC-3 via TCP/IP - Communication Settings
- Last UpdatedAug 01, 2025
- 1 minute read
To establish communication with a device, the associated Board, Port and I/O Device need to be correctly configured in Plant SCADA Studio's Topology activity.
If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to manually configure them, use the settings outlined below.
Boards
|
Field |
Value |
|---|---|
|
Board Type |
Enter TCPIP. |
|
Address |
Enter 0. |
|
I/O Port |
Leave this field blank. |
|
Interrupt |
Leave this field blank. |
|
Special Options |
Leave this field blank. |
Ports
|
Field |
Value |
|---|---|
|
Port Number |
Leave this field blank. |
|
Baud Rate |
Leave this field blank. |
|
Data Bits |
Leave this field blank. |
|
Stop Bits |
Leave this field blank. |
|
Parity |
Leave this field blank. |
|
Special Options |
Enter the destination IP address of Ethernet module. Use the following format: -Ia -Pn -T where: a = the destination IP address in standard Internet dot format. (For example, 192.9.2.60) n = the destination Port number. Often one physical port has several virtual ports, used for different purposes. Use this option only if you want to override the default of 2222. -T = forces the driver to use TCP (the default), rather than UDP (-U). |
I/O Devices
|
Field |
Value |
|---|---|
|
I/O Device Address |
Specify the Offlink Address in the form: PMM:C[options],u |
|
I/O Device Protocol |
Enter ABTCP3. |