Virtual Units Configuration
- Last UpdatedAug 04, 2025
- 1 minute read
Port configuration for the Global Virtual Unit
|
Field |
Value |
|---|---|
|
Port Name |
This field is user defined. |
|
Port number |
|
|
Board name |
Refers to the board previously defined in the Boards view. |
|
Baud rate |
Leave this field blank |
|
Data bits |
Leave this field blank |
|
Stop bits |
Leave this field blank |
|
Parity |
Leave this field blank |
|
Special Opt |
-I127.0.0.1 –P12345 -U |
|
Comment |
This field is user defined and is not used by the driver. |
Device configuration for the virtual unit
|
Field |
Value |
|---|---|
|
Name |
This field is user defined. |
|
Number |
This is a unique I/O device number. Note: Use a different number for each virtual unit as they should not be configured as a redundant pair. |
|
Address |
65534 |
|
Protocol |
DNPR |
|
Port name |
Refers to the port defined in the Ports view. |
|
Comment |
This field is user defined and is not used by the driver. |
Device configuration for the global virtual unit
|
Field |
Value |
|---|---|
|
Name |
This field is user defined. |
|
Number |
This is a unique I/O device number. Note: Use a different number for each virtual unit as they should not be configured as a redundant pair. |
|
Address |
65535 |
|
Protocol |
DNPR |
|
Port name |
Refers to the port defined in the Ports view. |
|
Comment |
This field is user defined and is not used by the driver. |