Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

Configure Display Properties for an Alarm Mode

  • Last UpdatedJul 18, 2023
  • 2 minute read

An alarm mode provides a way to group together any alarms that are currently in the same mode of operation. For example, you can use a mode to represent any alarms that are currently shelved or disabled. This allows you to configure global display properties that can be applied to an alarm as it moves into the specified mode of operation. For example, you can:

  • Define background and foreground colors that provide a visual representation of a mode on a graphics page.

  • Associate Genies with a mode that you can use as an alarm flag or icon.

    Note: You can only use the predefined modes that are included with Plant SCADA, that is, Shelved/Disabled.

To configure display properties for an alarm mode:

  1. In the Setup activity, select Alarming.

  2. On the menu below the Command Bar, select Alarm Modes.

  3. Add a row to the Grid Editor.

  4. Type the required information in each column, or in the fields in the Property Grid (see below for a description of the fields).

  5. Click Save.

Alarm Mode Properties

General Properties

Field

Description

Display Name

Can be used to provide a meaningful representation of a mode. You need to select a name from those available in the drop-down list, otherwise a compile error will be generated.

Short Name

Can be used to provide a short-form name that represents the mode. For example, you can use this short name as a label on an alarm flag.

Comment

Any useful comment.

Foreground Color

Defines the foreground color to display when an alarm is in the specified mode of operation. Transparent colors are not supported.

Background Color

Defines the background color to display when an alarm is in the specified mode of operation. Transparent colors are not supported.

Library Name

The name of library to which the associated Genies belong (see below).

Genie Name

The name of a Genie that you want to use as a visual representation of this mode. This allows the Genie to be used as an alarm flag (see Use Alarm Indicators).

Thumbnail Name

The name of a small Genie that you want to use as a visual representation of this mode. This allows the Genie to be used as a small icon that indicates alarm priority.

Project Properties

Property

Description

Project

The project in which the alarm mode is included.

See Also

Use Alarm Indicators

Shelve Alarms

Disable Alarms

In This Topic