Using the Express Communications Wizard
- Last UpdatedAug 04, 2025
- 1 minute read
To set up communication using the Plant SCADA Express Communications Wizard, you will need to provide an Address, an IP address and Port number.
-
Address
The address to use for an IEC 870-5-104 device is the common ADSU address. This value is configured on the device and will be a number between 1 and 65535.
-
IP address
The IP address of the device.
-
Port
The default port number for the IEC 870-5-104 protocol is 2404.
Note: It is recommended you use TCP protocol when setting up an IEC 870-5-104 device.
This information is placed in the Special Options field of the Ports settings by the Express Communications Wizard using the following format:
—I<device IP address> —P<port number> —<T (TCP)>
For example:
—I192.1.1.182—P2404 —T