APDU stands for Application Protocol Data Unit. The APDU settings allow you specify parameters for the actual data packet that is transmitted to the BACnet device.

Parameter name

Description

Allowable value

Default value

AckTimeOut

Time (in milliseconds) spent waiting for a reply to a message.

500 - 60000

6000

SegmentTimeout

Time (in milliseconds) spent waiting for a segment acknowledgment message.

500 - 60000

5000

Retries

Maximum number of times request message will be resent due to timeout on a request.

0 - 10

3

FrameSize

Maximum frame size.

50 -1476

1476

MaxSegments

Maximum number of segments which may be transmitted and/or received in one segmented message.

1 - 256

10

WindowSize

Maximum number of segments which can be transmitted before an acknowledgment is sent to the initiator.

1 - 127

5