[IOServer]AsyncConnect
- Last UpdatedJul 19, 2023
- 1 minute read
Determines whether Plant SCADA will follow its default behavior and attempt to connect to all configured I/O servers on start-up.
When the AsynConnect parameter is set to 1, Plant SCADA will defer the connection attempt for each I/O Server until that I/O Server is required.
This option may be required in order to speed up the start-up process on sites which have many I/O Servers that do not yet exist.
Allowable Values:
-
0 - (I/O Servers will be connected on start-up)
-
1 - (Connection of I/O Servers will be bypassed on start-up)
Default Value:
0