Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

Define Equipment References

  • Last UpdatedJul 18, 2023
  • 2 minute read

You can add equipment references to a Plant SCADA project. See Equipment References for more information.

To manually define an equipment reference:

  1. In the System Model activity, select Equipment.

  2. On the menu below the Command Bar, select References.

    The list of equipment references will display in the Grid Editor.

  3. Add a row to the Grid Editor.

  4. Type the required information in each column, or in the Property Grid (see below for a description of the properties).

  5. Click Save.

Equipment Reference Properties

General Properties

Property

Description

Cluster

The name of the cluster to which the equipment is assigned.

Equipment

The name of the main piece of Equipment to which referenced equipment is linked from.

Referenced Cluster

The name of the cluster to which the referenced equipment is assigned.

Referenced Equipment

The name of the Equipment that you want to reference (link to).

Referenced Item

The name of the item belonging to the "referenced" Equipment. If the Item is listed only that referenced item will be returned using EquipRefBrowse functions. If this field is left blank items belonging to the referenced equipment will be available.

Category

A category that will be used to filter equipment references using EquipRefBrowse functions. You can use any separator between filter strings. For example, "Equipment.MT", "Equipment-MT" and "Equipment:MT" are all valid.

If you are configuring an interlock, the Situational Awareness Starter Project provides the following categories (see Interlocks for definitions):

  • Interlock.Process

  • Interlock.Safety

  • Interlock.Permissive.

    Enter the whole name of the category type (for example, "Interlock.Pocess").

Order

A unique index per reference category that will be used in the ordering for the EquipRefBrowse functions.

Association

Controls the name of the association used in the AssEquipReferences Cicode function. For each reference, a super-genie association is created which uses the name specified in the Association column.

Note: Association names are also passed into the ‘meo_selector_xx’ genie instances on faceplates e.g ?MEO2?. See Configure Equipment Selection for Group Objects for more information.

Comment

Any useful comment. Enter a value of 254 characters or less.

Custom Properties

Property

Description

Custom1 .. Custom8

User-defined strings that can be used for filtering equipment when using the EquipRefBrowse functions (maximum 254 characters each).

Project Properties

Property

Description

Project

Name of project

See Also

Interlocks

EquipRefBrowseOpen

AlarmCountEquipment

TitleResults for “How to create a CRG?”Also Available in