AVEVA™ Plant SCADA

Read Parameters

  • Last UpdatedJul 07, 2025
  • 1 minute read

Parameter name

Description

Allowable value

Default value

UseReadMultiple

Specifies whether to use the ReadPropertyMultiple Service

1: Allow
0: Not allowed

1

FastPoll

The parameter has been deprecated.

SlowPoll

The parameter has been deprecated.

RetriesOnError

Maximum number of times read transaction will be re-transmitted in case when the message packet received from device is invalid

0 - 10

3

COVLifeTime

Sets the change-of-value (COV) subscription time (in seconds).

The driver attempts to use COV reporting for devices that support it. It subscribes to COV notifications for a period defined by COVLifeTime setting, and periodically updates the existing subscriptions. If COVLifeTime equals 0, then COV reporting is not used.

0 to 86400

3600

(1 hour)

COVExpireLag

Sets the period of time (in milliseconds) to update an existing subscription before it expires. The driver periodically updates existing COV subscriptions.

Equal to or greater than zero (0)

60000

(1 min)

COVCancelAtShutdown

Specifies whether to cancel COV subscriptions at driver shutdown

1: Cancel COV subscriptions 0: Do not cancel COV subscriptions

1