M340, TSX Quantum and Premium PLCs - Communication Settings

M340, TSX Quantum and Premium PLCs - Communication Settings

  • Last UpdatedJul 08, 2025
  • 1 minute read

The following tables show the settings for communication with TSX Quantum™ and Premium™ PLCs. To establish communication with a device, configure the Boards, Ports and I/O Devices settings in Plant SCADA Studio's Topology activity. If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to configure them manually, or verify that the fields are correct, use the settings outlined below.

Boards

Field

Value

Board Type

Enter TCPIP.

Address

Enter 0.

I/O Port

Leave this field blank.

Interrupt

Leave this field blank.

Special Options

Leave this field blank.

Ports

Field

Value

Port Number

A valid unique number.

Baud Rate

Leave this field blank.

Data Bits

Leave this field blank.

Stop Bits

Leave this field blank.

Parity

Leave this field blank.

Special Options

Enter the destination IP address of the PLC. Use the following format:

-Ia -Pn -T

where:

a = the IP address in standard Internet dot format. (For example 192.9.2.60)

n = the destination Port number. Often one physical port has several virtual ports, used for different purposes. Use this option only if you want to override the default of 502.

-T = forces the driver to use TCP, rather than UDP (-U).

I/O Device Settings

Field

Value

I/O Device Address

Leave this field blank. A value of 0 is assigned by default.

I/O Device Protocol

Enter the MODNET protocol variant.

(See MODNET Protocol Variants to determine which variant is required.)