[Alarm]IsolationDetectRetryCount

  • Last UpdatedJul 19, 2023
  • 1 minute read

This parameter sets the Internet Control Message Protocol (ICMP) retry count to detect network isolation on alarm servers. If ICMP check fails more times than this number in a row, the server will regard itself as isolated from the main network and then switch itself to isolated main state. The interval between ICMP packets is configured on [Alarm]IsolationDetectInterval.

This parameter is only valid if [Alarm]IsolationDetectIP1 and/or [Alarm]IsolationDetectIP2 parameters have been configured.

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

0-5

Default Value:

2