Logging Parameters
- Last UpdatedJul 08, 2025
- 2 minute read
|
|
|
UNINTENDED EQUIPMENT OPERATION Do not under any circumstances change or remove any of the undocumented citect.ini parameters. Before deleting sections of the citect.ini file, confirm that no undocumented parameters will be deleted. Failure to follow these instructions can result in death, serious injury, or equipment damage. |
|
[ABCLX] Parameter |
Description |
Allowable Values |
Default Value |
|
DebugLevel |
The trace level used for the log file. |
Any combination of the following, separated by a pipe character (|): ERROR WARN TRACE DEBUG ALL See Logging for examples. |
- |
|
DebugCategory |
The categories used for the log file. |
Any combination of the following, separated by a pipe character (|): TAG= Tag configuration trace SOCK= Socket trace EIP= EIP session trace DCB= Front-end driver trace BUFF= Dump a counted buffer to hex THREAD= Thread trace STATISTICS = All tags downloaded from PLC REPORT = All Plant SCADA tags subscribed VALIDATE = All optimized blocks the driver generated ALL = all of the above. See Logging for examples. |
- |
|
LogFileArchive |
This parameter has been deprecated. |
- |
- |
|
LogFileSize |
This- parameter has been deprecated. |
- |
- |
|
LogTagInfo |
If this parameter is enabled, the driver will log the following information to the I/O server syslog file:
See also Global and Device-Specific Parameters. |
0 or 1 |
0 |