Data Types

Address Format

Plant SCADA Data Type

Description/Special Usage/Limitations/ Valid Ranges

State

i1.i2.i3.i4:STATE

DIGITAL

Device status. 1 if it is responding, 0 if it is not responding. Read only.

Status

i1.i2.i3.i4:STATUS

INTEGER

Device status. 1 if it is responding, 0 if it is not responding. Read only.

Error Number

i1.i2.i3.i4:ERRNUM

INTEGER

A number representing the error condition of the last ping. Read only.
0: No faults
1: Not responding
2: Socket write timed out
3: Socket read timed out

Error Description

i1.i2.i3.i4:ERRDESC

STRING

A description of the status of the last ping. Read only.
Blank when no error, or,
not responding
socket write timed out
socket write not successful

Poll Time

i1.i2.i3.i4:POLLTIME

LONG

The duration, in seconds, between each ping to the host. See Driver Parameter HostPollTime for default.

Time Out

i1.i2.i3.i4:TIMEOUT

LONG

The time, in seconds, to wait for a response from the host after it is pinged.

Response Time

i1.i2.i3.i4:RESPTIME

LONG

The time, in milliseconds, it took the host to respond to the last ping. Read only.

Where:

I1

The first octet (most significant) of the IP address of the device to ping

I2

The second octet of the IP address of the device to ping

I3

The third octet of the IP address of the device to ping

I4

The fourth octet of the IP address of the device to ping

Examples

Data Type

DIGITAL

Address

192.168.1.1:STATE

Comment

FileServer01 state

Data Type

LONG

Address

192.168.1.1:RESPTIME

Comment

FileServer01 response time