AVEVA™ Plant SCADA

Structure of a Trap

  • Last UpdatedDec 17, 2021
  • 1 minute read

The table below shows the components of a trap PDU and the special tags used to manipulate them.

Component

Special tag

enterprise

T0

agent-addr

T1

generic-trap

T2

specific-trap

T3

time-stamp

T4

variable-bindings

T5, T6, TNVB and SubfieldNumber

  • variable-bindings is a list of VarBinds, each consisting of name (see T5) and value (see T6).

Note: Most SNMP traps only contain one record; however, it is possible to get a trap with many records. A mechanism exists using the "subfield number" to iterate and read all these trap records.