[Alarm.<ClusterName>.<ServerName>]DisableConnection
- Last UpdatedJul 19, 2023
- 1 minute read
This setting is used to specify whether or not the client sub system should connect to the given server. If the Citect.ini on a particular computer has [Type.ClusterName.ServerName]DisableConnection = 1 specified for a particular server, then the client sub system will establish a non-redundant connection to the other server in the redundant pair. If that connection becomes inoperative, the client sub system will not be redirected and will have no connection until the server is restored.
To define connection priority of a particular server use [Alarm.<ClusterName>.<ServerName>]Priority.
Note: This parameter needs to be applied to a specific alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.
Allowable Values:
-
0 - Allow the client to connect to the server
-
1 - Stop the client connecting to the server
Default Value:
0