To establish communication with a device, the associated Board, Port and I/O Device need to be correctly configured in Plant SCADA Studio's Topology activity.

If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to manually configure them, use the settings outlined below.

Boards

Field

Value

Board Type

Enter TCPIP.

Address

Enter 0.

I/O Port

Leave this field blank.

Interrupt

Leave this field blank.

Special Options

Leave this field blank.

Ports

Field

Value

Port Number

Leave this field blank.

Baud Rate

Leave this field blank.

Data Bits

Leave this field blank.

Stop Bits

Leave this field blank.

Parity

Leave this field blank.

Special Options

Enter the destination IP address of Ethernet module. Use the following format:

-Ia -Pn -T

where:

a = the destination IP address in standard Internet dot format. (For example 192.9.2.60)

n = the destination Port number. Often one physical port has several virtual ports, used for different purposes. Use this option only if you want to override the default of 2222.

-T = forces the driver to use TCP (the default), rather than UDP (-U).

I/O Devices

Field

Value

I/O Device Address

Specify the Offlink Address in the settings:

PMM:C[options],u

I/O Device Protocol

Enter ABTCP500.