Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

[Alarm]TransferConnectTimeout

  • Last UpdatedJul 19, 2023
  • 1 minute read

Defines the amount of time, in seconds, that the Primary server will wait for a connection to occur. This works in the same way as the MonitorConnectTimeout parameter, except that it applies to the server's attempts to establish a connection to the Standby Server for the purpose of transferring data (rather than establishing a connection for monitoring the other server).

Typically, the default setting is appropriate. You may need to increase the TransferConnectTimeout if the system incorrectly regards a connection as having been unsuccessful when it is still in the process of being established.

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

0 to 4294967295

Default Value:

30