Allen-Bradley SLC-500 via TCP/IP - Data Types

  • Last UpdatedAug 01, 2025
  • 2 minute read

Note: The Allen Bradley SLC500 has many data types. The protocol makes a separate request for each different data type, and each request has a finite overhead. It is more efficient to read fewer data types, so you should move the I/O and other data into a few main blocks to be read by Plant SCADA.

Data Types

Address Format

Plant SCADA Data Type

Status words

S:w/b

DIGITAL

Timer

Tf:w.t

DIGITAL

Timer

Tf:w/b

DIGITAL

Counter

Cf:w.c

DIGITAL

Counter

Cf:w/b

DIGITAL

Control

Rf:w.r

DIGITAL

Control

Rf:w/b

DIGITAL

Binary

Bf:w/b

DIGITAL

Integer

Nf:w/b

DIGITAL

Output image

O:O.o

INT

Input image

I:O.o

INT

Status words

S:w

BCD / INT / LONG / LONGBCD/ REAL

Timer

Tf:w.T

BCD / INT / LONG / LONGBCD/ REAL

Counter

Cf:w.T

BCD / INT / LONG / LONGBCD/ REAL

Control

Rf:w.C

BCD / INT / LONG / LONGBCD/ REAL

Binary

Bf:w

BCD / INT / LONG / LONGBCD/ REAL

Integer

Nf:w

BCD / INT / LONG / LONGBCD/ REAL

Where:

f

File Number 0 to 999 decimal

:w

Element number 0 to 999 decimal

:O

Element number 0 to 277 octal

/b

Bit Number 0 to 15 decimal

/o

Bit Number 0 to 17 octal

.T

Timer/Counter Sub Element:

PRE - Preset Value
ACC - Accumulated Value

.t

Timer bits:

EN - Enable
TT - Timing
DN - Done

.C

Control Sub Element:

LEN - Length
POS – Position

.c

Counter bits:

CU - Count Up
CD - Count Down
DN - Done
OV - Overflow
UN - Underflow

.r

Control bits:

EN - Enable
DN - Done
ER - Error
UL - Unload
IN - Inhibit comparisons
FD - Found

Examples

Data Type

DIGITAL

Address

N7:1/15

Comment

Integer - File Number 7 Element Number 1 Bit Number 15

Data Type

INT

Address

N7:3

Comment

Integer - File Number 7 : Element Number 3