GE Fanuc GERx3i via TCP/IP - Data Types

  • Last UpdatedAug 04, 2025
  • 1 minute read

Note: GETCP driver will not allow writing to individual bits in W register. User can write 16 bit value to W register.

Data Types

Address Format

Plant SCADA Data Type

Discrete Input

Ia

DIGITAL

Discrete Output

Qa

DIGITAL

System Register

Rf

INT, LONG, REAL, BCD, LONGBCD, STRING

Retentive Bulk Memory Register

Wi

INT, LONG, REAL, BCD, LONGBCD, STRING

Global

GAh

DIGITAL

Global

GBh

DIGITAL

Global

GCh

DIGITAL

Global

GDh

DIGITAL

Global

GEh

DIGITAL

Temporary Coil

Tg

DIGITAL

Momentary Coil

Ma

DIGITAL

System Status

Sb

DIGITAL (RO)

System Memory A

SAb

DIGITAL

System Memory B

SBb

DIGITAL

System Memory C

SCb

DIGITAL

Analog Input

AIc

INT, LONG, REAL, BCD, LONGBCD, STRING (RO)

Analog Output

AQc

INT, LONG, REAL, BCD, LONGBCD, STRING

PLC Fault Table

PLCFd

BYTE (RO)

IO Fault Table

IOFe

BYTE (RO)

Where

a

1 to 32768

b

1 to 128

c

1 to 32640

d

0 to 683

e

0 to 1355

f

1 to 32768

g

1 to 1024

h

1 to 1280

i

1 to 2621441

Note: Currently the maximum STRING length is 8 bytes. Only the first eight characters are written to the PLC and set the rest to zero. For example: assume the input value is "abcdefghijklmn" , the value in the PLC will be "abcdefgh\0\0\0\0\0\0".

Examples

Data Type

DIGITAL

Address

I0025

Comment

Discrete Digital Input 25

Data Type

INT

Address

R0100

Comment

System Register 100