[Alarm]AlarmListRequestTimeout

  • Last UpdatedJul 19, 2023
  • 1 minute read

This parameter specifies the length of time (in seconds) that an alarm display will wait to receive data from all clusters. If data is still outstanding at end of this period, the alarm list will display the data that is available and a timeout notification will be generated as a hardware alarm. You can use the Cicode function AlarmGetInfo (type 16) to capture these notifications. Any data that arrives after this timeout period will be displayed as it is received.

When this parameter is set to zero (or a value less than zero), no timeout notification will be generated.

Allowable Values:

–1 to 2147483647

Default Value:

10 (seconds)

See Also

Alarm Parameters