Parameter name

Description

Allowable value

Default value

DiscoveryRate

The discovery rate in milliseconds. Specifies the rate at which the driver sends a 'WhoIs' message for dynamic device binding.

Note: This parameter can only be used globally, it can not be set for a specific device.

If this parameter is set to 0, the driver will not perform the dynamic device discovery, so the I/O Device address should include the information in order to set up the connection to the device, e.g. device IP address, port number, etc.

Equal or greater than 0

20000

WhoIsMaxGap

Enables filtered device detection via WhoIs message. It Blocks adjacent or nearby Device Id numbers within 'WhoIsMaxGap' range into a single call to WhoIs message. A non zero value enables filtered device detection according to configured BacNet devices

0 to 65535

0: Use unfiltered device detection