Counter Parameters

  • Last UpdatedAug 04, 2025
  • 1 minute read

warning2

UNINTENDED EQUIPMENT OPERATION

Do not change these protocol parameters, except on the advice of Technical Support for this product.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Note: At times during the life cycle of a driver, circumstances may call for the creation of specific citect.ini parameters that remain undocumented. Always seek the advice of Technical Support regarding the possible implementation of undocumented parameters before you make any changes to a citect.ini file.

[IEC870IP] Parameter

Description

Allowable Values

Default Value

CounterPollTimeSec

Determines how often a counter interrogation is performed.

1 - 32767
(in seconds)

1800

CounterPollType

Determines the type of counter interrogation message that is sent.

0 – No freeze or reset

1 – Freeze without reset

2 – Freeze with reset

3 – Reset only

1