Communication Settings
- Last UpdatedSep 02, 2022
- 1 minute read
To establish communication with a device, the associated Board, Port and I/O Device need to be correctly configured in Plant SCADA Studio's Topology activity.
If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to manually configure them, use the settings outlined below.
Boards
Typically, you would use a serial board or COM port for this communication.
Board Type
Enter COMx.
Address
Enter 0.
I/O Port
Leave this field blank.
Interrupt
Leave this field blank.
Special Options
Leave this field blank.
Ports
Port Number
This value should match the COM port number. This number is defined in the Ports section of the Control Panel.
Baud Rate
This value must match the setting of the PCD - 9600 is the default.
Data Bits
Enter 8.
Stop Bits
Enter 1.
Parity
This protocol can use two different transmission methods: 1) a Parity changing method or 2) a Break method of transmission. The Plant SCADA SBUS driver uses as default the parity changing method. Run the SAIA PCD Programming Utilities to set the PLC the transmission method.
Special Options
You may want to use the Special Options for the COMx Driver if you are using a Modem (or similar) and want the driver to perform differently.
I/O Devices
I/O Device Address
The station address (1-90) configured on the PCD, for example:
-
1 specifies PCD address 1.
-
49 specifies PCD address 49.
I/O Device Protocol
Enter SBUS.