[Trend]ReloadBackOffTime

  • Last UpdatedJul 19, 2023
  • 1 minute read

Adding or updating trend records too quickly could potentially put pressure to the server disk, causing delays to server responsiveness or trend sample collection.

A back-off time can be configured to control the pace of the reload on a trend server. The back-off time represents the minimal number of milliseconds for which the system will wait after adding or updating a trend record. The system will not attempt to reload another trend record before this back-off time is out.

This configuration value is read at the beginning of each server reload.

Allowable Values:

  • 0 ~ 2147483647 (milliseconds)

Default Value:

1 (millisecond)

See Also

Trend Parameters

In This Topic
Related Links