Note: This command is now deprecated. Use AlmBrowseEnable function instead.

The AlmTagsEnable function enables the alarm tag at the current cursor position in an active data browse session.

This function is a non-blocking function. It does not block the calling Cicode task.

Syntax

INT AlmTagsEnable(INT iSession [, INT bAcknowledge])

iSession:

The handle to a browse session previously returned by a AlmTagsOpen call.

bAcknowledge:

Forces acknowledgment of an alarm after it is enabled. The accepted values are:

0 — (default) enforced acknowledgment will not be applied.

1 — alarm will be acknowledged when enabled.

Return Value

0 (zero) if the alarm browse session exists, otherwise an error code is returned.

AlmTagsAck, AlmTagsClear, AlmTagsDisable, AlmTagsClose, AlmTagsFirst, AlmTagsGetField, AlmTagsNext, AlmTagsNumRecords, AlmTagsOpen, AlmTagsPrev