AVEVA™ Plant SCADA

Data Types

  • Last UpdatedDec 13, 2021
  • 1 minute read

Omron's range of PLCs is logically split into three distinct series:

Omron PLC Series

PLC Model

Series 1

C Series - including C20, C**P, C**K, C120, C500, C1000H, C2000, C2000H, C**H, CPM1*, CPM2*, CQM1, CQM1H, C200H, C200HS, C200HE, C200HG, C200HX, IDSC and SRM1 PLCs

Series 2

CV, CVM1 Series - including all CV*** and CVM1 CPUs

Series 3

CP, CJ/CS, NSJ Series - including all CP1, CJ1, CS1 and NSJ controllers

Each series has the same memory areas, but different ranges. For this reason, the supported data types for each series are tabled separately.

The following notation is used within the tables:

Enclosing square brackets ([ ]) mean the content is optional and may be omitted.

In some cases, however (where the native tag type can be either DIGITAL or INT), the inclusion of optional content may define the tag type. For example:

  • CIO123 is INTEGER

  • CIO123.9 becomes DIGITAL (i.e. [.9] changes the tag's type)

Native type means default type for a given tag address.

No Write Command means that the tag is read-only.

S.MODE tag can be written to (unlike other status tags). The allowable write values are "Go to RUN mode" and "Go to MONITOR mode". For the OMFINS driver, RUN=2 and MONITOR=4.